Cerberus PRO

Cerberus PRO system overview

This fire safety system overview shows the most important system components of CerberusTM PRO – from powerful panels and clever fire detectors to smart peripheral devices.


The fire system overview graphic also depicts how the fire system components can be connected with each other:

C-NET – detector bus network for linking fire detectors and peripherals

The C-NET is a modern, multipurpose detector bus system that allows flexible planning and installation: all detectors and peripheral devices share the same loop. The C-NET devices of the fire system communicate and get their power supply directly via the C-NET – without additional cabling.

Cluster (C-WEB/SAFEDLINK) – network for linking panels and fire terminals

Up to 16 fire control panels and/or operator terminals can be networked in one cluster (C-WEB/SAFEDLINK) – if the fire system is connected to a danger management station. Without a danger management station, even 32 panels can be networked in one cluster.

Backbone (C-WEB/LAN) – LAN network for linking clusters

Up to 14 clusters with up to 16 panels each can be networked via an EN 54-approved fiber-optic backbone (C-WEB/LAN). Due to the backbone, Cerberus PRO can even depict highly complex building structures and organizational processes. This makes the backbone the ideal solution when planning a large and complex fire system for universities, for example, with buildings spread over an extensive campus.


Fire panels combine high security standards with latest technology

Fire panels and fire terminals from Cerberus PRO are ideal whatever the size or complexity of your application. They provide a quick, comprehensive overview of all messages generated by the fire safety system. Moreover, Cerberus PRO fire panels are easy and intuitive to operate. Customizable intervention texts enable correct actions of people in charge – which is highly important especially in stressful emergency situations.
The portfolio of our Cerberus PRO fire panels includes:

Fire control panels that meet your application requirement

CerberusTM PRO offers four fire control panels. They answer the different requirements from small and simple to large and complex application sites. All fire control panels can either stand alone or be networked. Even redundant, EN 54-approved networks are possible thanks to the Ethernet technology that is built into every panel.
The fire control panels process all system messages and trigger alarms. Every model provides a simple user interface and customizable user prompting texts. This makes the control panels easy-to-operate – and safe and correct action is ensured in case of an event. In addition, remote access for remote operation and servicing is possible.
The portfolio of fire control panels comprises:

Product, catalog link

Description, consists of

Loops, addresses

Power supply

Battery capacity

Cabinet dimensions (HxWxD)

FC721-ZZ

- Control unit
- Eco housing

1, max. 126

70 W

2x7 Ah

398x430x80

FC721-YZ

- Control unit with 24 LED display groups
- Eco housing

1, max. 126

70 W

2x7 Ah

398x430x80

FC722-ZZ

- Control unit
- Standard housing

2-4, max. 252

70 W

2x12 Ah

398x430x160

FC722-YZ

- Control unit with 24 LED display groups
- Standard housing

2-4, max. 252

150 W

2x12 Ah

398x430x160

FC722-ZA

- Control unit
- Comfort housing

2-4, max. 252

150 W

2x26 Ah

398x430x160

FC722-ZE

- Control unit with 48 LED display groups
- Comfort housing

2-4, max. 252

150 W

2x26 Ah

398x430x160

FC724-ZA

- Control unit
- Comfort housing

4-8, max. 504

150 W

2x26 Ah

398x430x160

FC724-ZE

- Control unit with 48 LED display groups
- Comfort housing

4-8, max. 504

150 W

2x26 Ah

398x430x160

FC726-ZA

- Control unit
- Comfort housing

4-8, max. 1,512

150

2x45 Ah

796x430x260